Cooling capacity = chilled water flow * 4.187 * temperature difference * coefficient
1. The chilled water flow refers to the cold water flow required for the operation of the machine, and the unit needs to be converted into liters per second;
2 , the temperature difference refers to the temperature difference between the machine inlet and outlet;
3 , 4.187 is the quantitative (specific heat capacity of water);
4. When selecting an air-cooled chiller, multiply the factor by 1.3 , and select a water-cooled chiller to multiply by a factor of 1.1 .
5. Select the appropriate machine model based on the calculated cooling capacity.
It is customary to use the P to calculate how much the chiller should be equipped with , but the main thing is to know the rated cooling capacity. If the air-cooled 9.07KW is used, choose a 3P machine . And so on. Therefore, the choice of industrial chiller is important to determine the rated cooling capacity.
How big is the industrial chiller?
How big is the industrial chiller?
Â
How to choose the industrial chiller that Zui is suitable for, in fact, it is very simple to have a selection formula: